OVERVIEW
UPC Code | 037332121455 |
UPS Type | Line-Interactive |
INPUT
Rated input current (Maximum Load) | 27A |
Nominal Input Voltage(s) Supported | 230V AC |
UPS Input Connection Type | Hardwire |
UPS Input Connection Description | Hardwire input supports International 230V input (L, N, PE) |
Input Phase | Single-Phase |
OUTPUT
Output Volt Amp Capacity (VA) | 5000 |
Output Capacity (kVA) | 5 |
Output Watt Capacity (Watts) | 3750 |
Output kW Capacity (kW) | 3.75 |
Power Factor |
0.75 | |
Nominal Voltage Details | 230v nominal inverter output voltage |
Frequency Compatibility | 50 / 60 Hz |
Frequency Compatibility Details | Automatic frequency selection |
Output Voltage Regulation (Line Mode) | -17%, +8% |
Output Voltage Regulation (Battery Mode) | +/- 5% |
Included Output Power Cables | Includes 3 C13 to C14 output power cables |
Output Circuit Breakers | 15A (x3) breaker supports 1 C19 outlet each, 10A (x2) breaker supports 4 C13 outlets each |
Output AC Waveform (AC Mode) | Sine wave |
Output AC Waveform (Battery Mode) | Pure Sine wave |
Nominal Output Voltage(s) Supported | 220V; 230V; 240V |
Output Receptacles | (8) C13; (3) C19 |
Individually Controllable Load Banks |
No |
BATTERY
Battery Type | Valve Regulated Lead Acid (VRLA) |
Full Load Runtime (min.) |
8.5 min. (3750w) | |
Half Load Runtime (min.) |
20 min. (1875w) | |
Expandable Battery Runtime | Extended runtime supported via optional external battery packs |
Expandable Runtime | Yes |
External Battery Pack Compatibility |
BP48V24-2U (limit 1); BP48V60RT-3U (multi-pack compatible); BP48V27-2US (multi-pack compatible) | |
DC System Voltage (VDC) | 48 |
Battery Recharge Rate (Included Batteries) | Less than 4 hours from 10% to 90% (typical, full load discharge) |
Battery Access | Front panel battery access door |
Internal UPS Replacement Battery Cartridge | RBC94-3U (quantity 3) |
Battery Replacement Description | Hot-swappable, user replaceable batteries |
VOLTAGE REGULATION
Voltage Regulation Description | Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 170 to 282 |
Overvoltage Correction |
Input voltages between 245 and 282 are reduced by 12% | |
Undervoltage Correction |
Input voltages between 170 and 199 are boosted by 12% |
USER INTERFACE, ALERTS & CONTROLS
Switches | 2 Switches control off/on power status and alarm-cancel/self-test operation |
Alarm Cancel Operation | Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate low-battery status |
Audible Alarm | Audible alarm indicates power-failure, overload and low-battery conditions |
LED Indicators | 5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status |
SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating | 480 |
UPS AC Suppression Response Time | Instantaneous |
EMI / RFI AC Noise Suppression |
Yes |