OVERVIEW
UPC Code 037332121455
UPS Type Line-Interactive
INPUT
Rated input current (Maximum Load) 27A
Nominal Input Voltage(s) Supported 230V AC
UPS Input Connection Type Hardwire
UPS Input Connection Description Hardwire input supports International 230V input (L, N, PE)
Input Phase Single-Phase
OUTPUT
Output Volt Amp Capacity (VA) 5000
Output Capacity (kVA) 5
Output Watt Capacity (Watts) 3750
Output kW Capacity (kW) 3.75
Power Factor
0.75
Nominal Voltage Details 230v nominal inverter output voltage
Frequency Compatibility 50 / 60 Hz
Frequency Compatibility Details Automatic frequency selection
Output Voltage Regulation (Line Mode) -17%, +8%
Output Voltage Regulation (Battery Mode) +/- 5%
Included Output Power Cables Includes 3 C13 to C14 output power cables
Output Circuit Breakers 15A (x3) breaker supports 1 C19 outlet each, 10A (x2) breaker supports 4 C13 outlets each
Output AC Waveform (AC Mode) Sine wave
Output AC Waveform (Battery Mode) Pure Sine wave
Nominal Output Voltage(s) Supported 220V; 230V; 240V
Output Receptacles (8) C13; (3) C19
Individually Controllable Load Banks
No
BATTERY
Battery Type Valve Regulated Lead Acid (VRLA)
Full Load Runtime (min.)
8.5 min. (3750w)
Half Load Runtime (min.)
20 min. (1875w)
Expandable Battery Runtime Extended runtime supported via optional external battery packs
Expandable Runtime Yes
External Battery Pack Compatibility
 BP48V24-2U  (limit 1);  BP48V60RT-3U  (multi-pack compatible);  BP48V27-2US  (multi-pack compatible)
DC System Voltage (VDC) 48
Battery Recharge Rate (Included Batteries) Less than 4 hours from 10% to 90% (typical, full load discharge)
Battery Access Front panel battery access door
Internal UPS Replacement Battery Cartridge  RBC94-3U  (quantity 3)
Battery Replacement Description Hot-swappable, user replaceable batteries
VOLTAGE REGULATION
Voltage Regulation Description Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 170 to 282
Overvoltage Correction
Input voltages between 245 and 282 are reduced by 12%
Undervoltage Correction
Input voltages between 170 and 199 are boosted by 12%
USER INTERFACE, ALERTS & CONTROLS
Switches 2 Switches control off/on power status and alarm-cancel/self-test operation
Alarm Cancel Operation Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate low-battery status
Audible Alarm Audible alarm indicates power-failure, overload and low-battery conditions
LED Indicators 5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status
SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating 480
UPS AC Suppression Response Time Instantaneous
EMI / RFI AC Noise Suppression
Yes
PHYSICAL
Primary Form Factor Rackmount
Cooling Method Fans
Installation Form Factors Supported with Included Accessories 4 post 19 inch rackmount
Installation Form Factors Supported with Optional Accessories 2 post rackmount ( 2POSTRMKITHD ); Tower ( 2-9USTAND )
Minimum Required Rack Depth with External Battery Pack (cm) 81
Minimum Required Rack Depth with External Battery Pack (in.) 32
Minimum Required Rack Depth without External Battery Pack (cm) 72
Minimum Required Rack Depth without External Battery Pack (in.) 28.5
Primary UPS Depth (mm) 635
Primary UPS Height (mm) 132
Primary UPS Width (mm) 445
Rack Height 3U
Shipping Dimensions (hwd / cm) 28.58 x 57.20 x 80.01
Shipping Weight (kg) 82.55
UPS Housing Material Steel
UPS Power Module Dimensions (hwd, cm) 13.21 x 44.45 x 63.50
UPS Power Module Weight (kg) 64.86
ENVIRONMENTAL
Operating Temperature Range +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Storage Temperature Range +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Relative Humidity 0 to 95%, non-condensing
AC Mode BTU / Hr. (Full Load)
271
Battery Mode BTU / Hr. (Full Load)
1267
AC Mode Efficiency Rating (100% Load) 98%
Audible Noise 45 dBA maximum, front side 1m
COMMUNICATIONS
Network Management Cards  SNMPWEBCARD ;  TLNETCARD ;  WEBCARDLX
Network Monitoring Port Description Supports detailed monitoring of UPS and site power conditions
PowerAlert Software For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at https://www.tripplite.com/poweralert
Communications Cable USB and DB9 cabling included
WatchDog Compatibility Supports Watchdog application, OS and hard-reboot restart options for remote applications
Network Management Card Description Network management card optional
Communications Interface DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface; USB
LINE / BATTERY TRANSFER
Transfer Time
7 ms (AC to Battery); 1 ms (Battery to AC) typical
Low Voltage Transfer to Battery Power (Setpoint) 170
High Voltage Transfer to Battery Power (Setpoint) 282
FEATURES & SPECIFICATIONS
Grounding Lug Back panel grounding lug
Cold Start (Startup in Battery Mode During a Power Failure) Cold-start operation supported
High Availability UPS Features
Auto Probe Monitoring (requires WEBCARDLX); Automatic Voltage Regulation (AVR); Expandable battery backup; Hot swappable batteries; Remote management; Sine wave output; Surge/noise protection
Green Energy-Saving Features Greater than 95% efficiency – GREEN UPS
STANDARDS & COMPLIANCE
UPS Certifications CE
Certification Details Class A (EMI)
WARRANTY
Product Warranty Period (International) 2-year limited warranty
SmartPro 230V 5kVA 3.75kW Line...