OVERVIEW
UPC Code037332185631
UPS TypeOn-Line
INPUT
Rated input current (Maximum Load)14.97A
Nominal Input Voltage(s) Supported200V AC; 208V AC; 220V AC; 230V AC; 240V AC
UPS Input Connection TypeC20 inlet
Input PhaseSingle-Phase
OUTPUT
Output Volt Amp Capacity (VA)3000
Output Capacity (kVA)3
Output Watt Capacity (Watts)2700
Output kW Capacity (kW)2.7
Output Capacity DetailsDE-RATING INFORMATION: Max output in Frequency Conversion mode is reduced to 1890 watts for 208/220/230/240V output voltages; Max output is reduced to 2160W at 200V output voltage in all operating modes OVERLOAD CAPACITY: Supports inverter operation up to 105% load continuously, 125% for 3 minutes, 150% for 30 seconds and >150% for 0.5 seconds before switching to BYPASS (when bypass input voltage and frequency are WITHIN bypass limits) or SHUTDOWN (when bypass input voltage or frequency are OUTSIDE bypassed limits).
Power Factor
0.9
Crest Factor
3:1
Nominal Voltage DetailsThe nominal output voltage is user configured on first power-on
Frequency Compatibility50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion
Frequency Compatibility DetailsOutput frequency matches input nominal on startup; Output capacity de-rates by 30% during frequency conversion operation
Output Voltage Regulation (Line Mode)+/- 2%
Output Voltage Regulation (Economy Line Mode)+/- 10%
Output Voltage Regulation (Battery Mode)+/- 2%
Included Output Power CablesIncludes 2 C13 to C14 and 1 C19 to C20 power cables
Load Management Receptacles
Two switchable 4 outlet load banks (3 C13 and 1 C19 per bank)
Output AC Waveform (AC Mode)Pure Sinewave
Output AC Waveform (Battery Mode)Pure Sinewave
Nominal Output Voltage(s) Supported200V; 208V; 220V; 230V; 240V
Output Receptacles(8) C13; (2) C19
Individually Controllable Load Banks
Yes
BATTERY
Battery TypeValve Regulated Lead Acid (VRLA)
Full Load Runtime (min.)
5 min. (2700w)
Half Load Runtime (min.)
13.5 min. (1350w)
Expandable Battery RuntimeSupports extended runtime with optional external battery packs
Expandable RuntimeYes
External Battery Pack Compatibility
 BP72V15-2U  (limit 1);  BP72V28RT-3U  (multi-pack compatible);  BP72V18-2US  (multi-pack compatible)
DC System Voltage (VDC)72
Battery Recharge Rate (Included Batteries)3.0 hours from 10% to 90% (typical, full load discharge)
Battery AccessFront panel battery access door
Internal UPS Replacement Battery Cartridge RBC72S
Battery Replacement DescriptionHot-swappable, replaceable batteries
VOLTAGE REGULATION
Voltage Regulation DescriptionOnline, double-conversion power conditioning
Overvoltage Correction
2% output voltage regulation during overvoltages to 288
Undervoltage Correction
2% output voltage regulation during undervoltages to 160V (100% load), 130V (70% load), 100V (30% load)
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD DisplayInteractive front-panel LCD interface reports UPS operating mode, detailed UPS status, and site-power information; LCD interface also enables a variety of advanced UPS setup and configuration options
Switches5 front panel switches: On/Off, Up, Down, and Escape
Alarm Cancel OperationThe power-fail alarm can be silenced by following on-screen prompts
Audible AlarmAudible alarm indicates power failure, low battery, overload, and fault
LED Indicators4 front panel LEDs: AC input (green), AC output (green), Battery (yellow), Fault (red)
SURGE / NOISE SUPPRESSION
UPS Dataline Suppression DetailsSingle line dialup/network data line protection included
EMI / RFI AC Noise Suppression
Yes
AC Suppression Joule Rating
570
AC Suppression Response Time
Instantaneous
PHYSICAL
Primary Form FactorRackmount
Cooling MethodFan
Included Mounting Accessory Description4 post installation accessories included
Installation Form Factors Supported with Included Accessories4 post 19-inch rackmount
Installation Form Factors Supported with Optional Accessories2 post rackmount ( 2POSTRMKITWM ); 2-4 post front rail rackmount ( UPSHDEARKIT ); Tower ( 2-9USTAND )
Minimum Required Rack Depth with External Battery Pack (cm)77
Minimum Required Rack Depth with External Battery Pack (in.)30.25
Minimum Required Rack Depth without External Battery Pack (cm)70
Minimum Required Rack Depth without External Battery Pack (in.)27.75
Primary UPS Depth (mm)616
Primary UPS Height (mm)88
Primary UPS Width (mm)438
Rack Height2U
Shipping Dimensions (hwd / cm)24.00 x 59.99 x 76.00
Shipping Weight (kg)39.01
UPS Housing MaterialMetal
UPS Power Module Dimensions (hwd, cm)8.79 x 43.79 x 61.60
UPS Power Module Weight (kg)31.17
ENVIRONMENTAL
Operating Temperature Range+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius.
Storage Temperature Range+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius.
Relative Humidity5 to 95%, non-condensing
AC Mode BTU / Hr. (Full Load)
933
AC Economy Mode BTU / Hr. (Full Load)485
Battery Mode BTU / Hr. (Full Load)
1399
AC Mode Efficiency Rating (100% Load)>90%
AC Economy Mode Efficiency Rating (100% Load)>95%
Audible Noise<50dB at front side 1M
Operating Elevation (m)Up to 3000m
COMMUNICATIONS
Network Management Cards SNMPWEBCARD;  WEBCARDLX
PowerAlert SoftwareFor local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at https://www.tripplite.com/poweralert
Communications CableUSB and DB9 cabling included
WatchDog CompatibilitySupports Watchdog application, OS and hard-reboot restart options for remote applications
Network Management Card DescriptionNetwork management card optional
Communications InterfaceContact closure; DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface; USB (HID enabled)
LINE / BATTERY TRANSFER
Transfer Time
No transfer time (0 ms.) in online, double-conversion mode; 4 ms. transfer time during economy mode operation
Low Voltage Transfer to Battery Power (Setpoint)160V (100% load), 140V (66% load), 120V (33% load)
High Voltage Transfer to Battery Power (Setpoint)288V
FEATURES & SPECIFICATIONS
Grounding LugBack panel grounding lug included
Cold Start (Startup in Battery Mode During a Power Failure)Cold-start operation supported
High Availability UPS Features
Auto Probe Monitoring and Reboot (requires WEBCARDLX); Automatic inverter bypass; Expandable battery backup; Hot-swappable batteries; On-Line/Double-Conversion; Remote management; Sine wave output; Surge/noise protection; Zero transfer time
Green Energy-Saving FeaturesHigh-efficiency economy mode operation; Individually controllable load banks
STANDARDS & COMPLIANCE
UPS CertificationsCE; ENERGY STAR Qualified; Meets FCC Part 15 Category A (EMI); Tested to CSA (Canada); Tested to EAC (Belarus, Kazakhstan, Russia); Tested to SASO (Saudi Arabia); Tested to UL1778 (USA)
Certification DetailsMeets EMI approvals IEC62040-2:2006; FCC Part 15
Tripplife SUINT3000LCD2U Smart...